ISO-Rated Spaces Specifying Luminaires for Highly Specialized ISO-Rated Spaces
Cleanrooms are facilities dedicated to specialized industrial manufacturing or scientific research. Typical cleanroom owners produce pharmaceuticals, integrated circuits, and LED monitors and televisions. Food processing facilities are highly driven by the need to keep food free from contamination, so cleanrooms are often utilized for these applications.

ISO Cleanroom Ratings: A Primer
Cleanrooms are categorized by their ability to clean particulates in a specific area. Based on the room’s ability to keep the air clean, the International Standards Organization assigns an ISO Cleanroom Rating. The room is cleaned by turning the air over via a high efficiency particulate air (HEPA) filtration system, which filters the air in per cubic meter as it flows through the system (particles/m^3). Cleanrooms are classified by the number of particles of each size that are allowed to penetrate into the room as outlined in the table below.
| ISO Class | Maximum concentration limits (particles/m3 of air) for particles equal to and larger than the size listed below | |||||
|---|---|---|---|---|---|---|
| 0.1 micron | 0.2 micron | 0.3 micron | 0.5 micron | 1 micron | 5 micron | |
| 1 | 2 | |||||
| 2 | 24 | 10 | 4 | |||
| 3 | 1 | 237 | 102 | 35 | 8 | |
| 4 | 10 | 2,370 | 1,020 | 352 | 83 | |
| 5 | 100 | 23,700 | 10,200 | 3,520 | 832 | 29 |
| 6 | 1000 | 237,000 | 102,000 | 35,200 | 8,320 | 293 |
| 7 | 10,000 | 1,002,000 | 352,000 | 83,200 | 2,930 | |
| 8 | 100,000 | 3,520,000 | 832,000 | 29,300 | ||
| 9 | (1.0x109) | 8,320,000 | 293,000 | |||
The above graphic demonstratoes the relativity of particle sizes.
The Right Fixture for the Right Space
The diagram above demonstrates how Kenall luminaires integrate into a cleanroom environment.
While luminaires themselves do not carry ISO ratings, they are designed with specific features that support the stringent requirements of ISO rated spaces. When specifying lighting for these spaces, their design must support the specific ISO rating of their intended application. The following is a general guideline of ISO rated applications:
| ISO 3 and 4 | ISO 5, 6, 7 and 8 | ISO 9 |
|---|---|---|
|
|
|
Specifying Lighting for ISO Rated Spaces
ISO 1 and ISO 2 Cleanrooms are extremely specialized and rare. So rare, in fact, that very few exist in the world, and as a result, very few lighting manufacturers build luminaires suitable for these applications. Kenall manufactures lighting products suitable for most cleanroom applications. Full integration into the cleanroom requires the following specialized lighting capabilities:
- Seal
The luminaire has to seal to the cleanroom ceiling.
- Withstand Air Pressure
The luminaire must withstand the HVAC air pressure without bleeding air into the room prior to traveling through the HEPA filtration system (fan filter unit/FFU).
- Maintainable
The luminaire must be maintained without breaking the seal to the ceiling. Generally, this is solved by using an ingress barrier door, which allows access to the inside of the luminaire via stainless steel fasteners, avoiding the need for room recertification